SEDEMAC's new GC2100 is a feature-rich control solution for a wide range of genset engines. Our product offers automation features such as AMF (auto-mains failure), auto exerciser etc. The full HD graphics LCD firmware incorporates useful counters such as mains & genset energy meters, engine run meter and more

  • Built in BTS battery monitoring : Reduces fuel consumption in telecom tower gensets by keeping the genset OFF even when the mains is unavailable by monitoring the 48V battery level
  • BTS battery monitoring and cyclic start/stop modes for low fuel consumption
  • Offers large number of digital /analog inputs and outputs in its class
  • Full graphics backlit LCD with power saving mode
  • Supports Auto (AMF, remote start /stop modes and cyclic mode) and manual modes; monitors 3-ph voltage and frequency for generator and mains; monitors 3-ph load current for generator and mains and power factor for generator
  • Monitors engine safety parameters through both analog resistive and digital switch sensors (e.g - lube oil pressure, engine temperature, fuel level)
  • Controls starter relay, fuel stop relay, alarm hooter and more
  • Supports the battery charging alternator I/O interface
  • Versatile software capable of saving "events" during operation; event log for 100 events with real time clock (RTC) stamps and engine run hour information
  • Deep Sleep Mode is a useful feature to prolong the battery life by suspending the normal functions of the controller
  • Incremental counters for engine starts, engine trips, engine run hour, genset kWh, kVAh, kVArh
  • Measures mains kW, kVA, kWh, kVAh, etc.
  • RS 485 (using MODBUS Protocol) for communicating with other devices
  • Supports parameter configuration at OEM's sites
  • Access to each parameter through PC software or keypad
  • PC connectivity via USB port and RS485
  • Monitoring screens and alarms are available with language options
# Feature SEDEMAC GC2100 Deep Sea DSE 7310 / 7320 ComAp InteliLit AMF25
0 Overall size 207 x 160 mm2 240 x 181 mm2 210 x 150 mm2
1 AMF, manual & auto-start functions DSE7320: Present
DSE7310: All Present, except AMF
2 Standard features: Engine & Genset protection, charging alternator I/O interface, License-free PC software connectivity via USB port, warming & shutdown alarms, low power standby, real time clock based event logs & scheduler, engine speed sensing (through magnetic pickup)
3 Industry standard IEC, CE certification for environmental protection and reliability, IP65 front with gasket (Optional)
4 Configurable digital outputs (for fuel, crank, and lot more) 7 6 7
5 Configurable analog inputs (for lube oil, temp, fuel level) 7 3 3
6 Configurable digital inputs (for lube oil, temp, fuel level and lot more) 9 9 7
7 Potential-free configurable outputs x 2 x
8 Measurement of 1-ph and 3-ph altemator & mains currents, real / apparent / reactive power, power factor, energy counter
9 Remote communication via RS485-MODBUS

Environmental Specifications

  • Operating/Storage Temperature: -20°C to 65°C as per IEC 60068-2-1, 2
  • Vibration: 2G in X, Y, Z for 8 Hz-500 Hz as per IEC 60068-2-6
  • Humidity: 0% to 95% RH as per IEC 60068-2-78
  • EMI/EMC: Compliance as per IEC 61000-6-2, 4
  • Power Supply: 8V - 32V DC continuous; power transients as per ISO 7637-2
  • Ingress Protection: IP65 for front face with optional gasket as per IEC 60529
  • Shock: 15 g for 11 mS, compliance as per IEC 60068-2-27

Technical Specifications

  • Power Consumption: ~0.15A @ 12V or 24V (standby mode)
  • Crank-start Dropout Survival Period: 50 mS for a drop from 12V
  • Charging Alternator Interface:
    0.2A @ 12V; 0.125A @ 24V
    Diagnostic voltage measurement
  • Digital Output:
    5 x 1A high-side drivers configurable for pre-heat, hooter, etc
    2 x 5A high-side drivers configurable for start relay, stop solenoid, fuel relay, contactors, etc.
  • Digital Input: 9 switch-to-ground inputs configurable for lube oil, temp, fuel level etc.
  • Analog Input:
    5 x resistive inputs (0kΩ-5kΩ); fully configurable for various sources
    2 x 4mA - 20 mA inputs / 0-5V inputs
    1 x differential input (±60V DC) for BTS battery voltage
  • Mains/Genset Voltage Measurement: 20V –300V AC RMS @ 3-75 Hz for Ph to N
  • Load Current Measurement: 0A - 5A AC RMS for current transformer (CT) secondary
  • Dimensions:
    External dimensions: 207mm x 160 mm x 38.5 mm
    Mounting panel cut: 189mm x 143 mm